UK - Domestic Water Pipe Sizing Methods

There are three common methods for domestic water pipe sizing in the UK, as described in the CIBSE/ SoPHE Technical Bulletin 16-01:


Residential:


BS EN 806.3:2006


Commercial:


BS 8558:2015 (formerly BS6700)


CIPHE Design Guide (similar to CIBSE Guide G and an extension from the Institute of Plumbing)


Each pipe sizing method works by assigning loading units to individual fixtures. Fixtures that use higher volumes of water are generally assigned higher loading unit values.


As more loading units are connected to a pipe, the higher the peak flow rate becomes. This is because it is assumed that more fixtures are likely to operate simultaneously.


All three pipe sizing methods determine the 'peak' flow rate (the 99th percentile) using a conversion from loading units. However, each method has its own unique difference that is explained below.


BS EN 806.3:2006


This pipe sizing method is recommended to be used for residential building designs.


The conversion from loading units (2) to a flow rate (1) can be seen in the below chart.


design flow rate figure

What is unique about this method is that the fixture with the largest loading unit (3) plays an important part in the calculation.


For example:


A pipe that is supplying four baths (4 loading units each) has 16 loading units.


pipe with 4 loading units each

A pipe that is supplying eight showers (2 loading units each) also has 16 loading units.

pipe design supplying 8 showers

However, as you can see in the images above, the pipe that is supplying the 16 loading units has a different peak flow rate result.


When the largest loading unit connecting to the pipe is 4, the peak flow rate is 0.616 L/sec.


When the largest loading unit connecting to the pipe is 2, the peak flow rate is 0.472 L/sec.

BS 8558:2015


This pipe sizing method is recommended to be used for commercial building designs.


The conversion from loading units to a flow rate can be seen in the below chart.



conversion from loading units chart

This conversion is much simpler than BS EN 806.3:2006 because it does not factor in the largest fixture loading unit that is connected to the pipe.


This method generally provides higher flow rates than BS EN 806.3:2006 as it assumes the number of fixtures that could operate simultaneously in a commercial building is higher than in a residential building.


For example:


A pipe that is supplying four baths (10 loading units each) has 40 loading units which convert to a peak flow rate of 0.670 L/sec. This is higher than BS EN 806.3:2006.


pipe design supplying 4 baths

A pipe that is supplying eight showers (3 loading units each) has 24 loading units which convert to a peak flow rate of 0.488 L/sec. This is higher than BS EN 806.3:2006.


pipe design supplying 8 showers


CIPHE Design Guide


This pipe sizing method is recommended to be used for commercial building designs and is an alternative to BS 8558:2015.


The conversion from loading units to a flow rate uses the same chart as BS 8558:2015. However, the key difference between the two methods is that the CIPHE Design Guide has options for the loading unit of each fixture based on how often the fixture is expected to be used.


As shown below, when the fixture's frequency of usage gets lower, the loading units assigned to the fixture are lower too.


frequency of use plumbing design guide

'Low' frequency = 20 minutes time difference between each use


'Medium' frequency = 10 minutes time difference between each use


'High' frequency = 5 minutes time difference between each use


Low frequency of use occurs where there is a single person or small group. High frequency of use occurs in buildings such as sports stadiums where there is a large group of people.


For example:


In a 'low' frequency of use building such as an office, a pipe that is supplying five basins (1 loading unit each) and five WCs (1 loading unit each) has 10 loading units which convert to a peak flow rate of 0.300 L/sec.


pipe design supplying 5 basins 10 units

In a 'high' frequency of use building such as a stadium, a pipe that is supplying five basins (4 loading units each) and five WCs (5 loading units each) has 45 loading units which convert to a peak flow rate of 0.720 L/sec.


pipe design supplying 5 basins

Additional Information to Consider When Pipe Sizing


Combining Hot and Cold Water Loading Units


It is important to know whether the tapware that is used for each fixture will consist of two outlets (one for hot and one for cold) or one outlet (either hot or cold).


If the hot and cold water at a fixture can operate simultaneously, this will lead to an increased number of loading units on your pipe and consequently a higher flow rate.


For example:


Using the BS EN 806.3:2006 pipe sizing method, a pipe that supplies 100 basins that have a separate outlet for hot and cold water will convert to a flow rate of 1.40 L/sec.

pipe design supplying 100

If those 100 basins shared an outlet for hot and cold water, the loading units will be significantly less and will convert to a flow rate of 1.05 L/sec.


conversion to a lower rate of 1.050

Other Water Requirements


When sizing pipes, it is important to consider more than the fixtures that are shown by the architect. There may be other water requirements on the project too such as mechanical boilers.


These items will not have loading units that are pre-defined because they are unique and project-specific.


To allow for these in your design, you will need to estimate a suitable load to assign to them based on their technical requirements.


For example:


Using the BS 8558:2015 pipe sizing method, a pipe that supplies 100 loading units will convert to 1.25 L/sec.


If you estimate the load from the mechanical boilers is equivalent to 5 loading units, the load will be allowed for in the upstream pipe and the flow rate is therefore increased to 1.293 L/sec.



mechanical boilers 5 unit graphic

Continuous Flow Rates


Not all water requirements should be diversified. A supply to an irrigation system that is known to operate at 100% demand (2 L/sec) every day at 10am should be incorporated into the pipe sizing methodology accordingly.


For example:


Using the BS 8558:2015 pipe sizing method, a pipe that supplies 100 loading units will convert to 1.25 L/sec.


Because the irrigation system could operate at the same time as the peak usage of the building fixtures, the 2 L/sec should be combined directly with it (not combined and diversified).


This will result in a peak flow rate of 3.25 L/sec.

peak flow rate pipe irrigation image

H2X - Pipe Sizing Tool


All of the different pipe sizing methods mentioned in this blog are included in H2X's design and calculation tool.


In addition to providing you with accurate flow rates based on your design layout, H2X will also calculate the velocities, pressures, and heat loss in your system.


Once you have completed your design, H2X will export the layout into AutoCAD or Revit.